Oxytreat S: Advanced Oxygen Scavenger for Boilers

URSA Associates offers Rochem Oxytreat S, an advanced oxygen scavenger tailored for boilers. This formulation, consisting of sodium sulfite with a specialized catalyst, enhances the reaction with dissolved oxygen, especially effective at lower temperatures.

Oxytreat - S

Purpose

  • Effective Oxygen Removal:Oxytreat S, composed of sodium sulfite with a specialized catalyst, accelerates the reaction with dissolved oxygen, particularly at low temperatures.
  • Optimal for Boilers:Ideal for water tube boilers operating below 60 atmospheres (850 psi).
  • Corrosion Prevention:Eliminates trace dissolved oxygen that can cause corrosion and failures in boiler metal and tubes, even with modern deaeration equipment.
  • Versatile Use:Particularly useful in low-temperature feed water systems, cold water systems, and for standby boilers to prevent corrosion during downtime.

Feed Requirements

  • Preparation:Solutions should be prepared with minimal stirring. Can be fed alone or with other treatment chemicals not affected by a reducing agent.
  • Dosage:Approximately fifty liters of Oxytreat S is required to react chemically with one part of dissolved oxygen. Fresh feed solutions are recommended daily.

Method of Feeding

  • Continuous Feeding:Recommended to the storage section of the deaerator or makeup tank. This ensures residual presence in the feed water system and boiler, even during higher-than-normal makeup requirements.
  • Equipment:Diaphragm or piston-type reciprocating positive displacement pumps or bypass feeders are suitable for feeding. A floating lid helps prevent reaction with atmospheric oxygen.

Control

  • Monitoring: Controlled by the sulfite test, aiming for a free residual of 30 to 60 ppm in boiler water. Standard iodometric titration is used for checking, with test units available from Rochem service engineers.

Dosage

  • Usage Table: The dosage of Oxytreat S needed to achieve the desired free sulfite reading in ppm as SO3 is provided in a table based on different pressure ranges.

How to Use:

  • Determine the sulfite as ppm SO3 in the boiler water through testing.
  • Find the sulfite range in the table that contains the measured free sulfite residual (ppm SO3).
  • Read the required ml of Oxytreat-S per 1000 liters (or per metric ton) under the appropriate pressure column.